At work, we often encounter customers with questions about which flowmeter to use to measure steam flow. Here we introduce a commonly used flowmeter for steam measurement for reference.
Steam flow measurement - vortex flowmeter principle:
First of all, the steam flowmeter-vortex flowmeter is based on the principle of Karman vortex street. When the gas encounters the triangular column of the vortex generator, a Karman vortex will be generated, which is converted into a frequency signal by the vortex piezoelectric ceramic probe and recorded by the signal board. Processing can calculate the flow value. At present, the most widely used is the measurement of steam, of course, it can also be used to measure the flow of liquid. Its main advantage is that the pressure loss is small, the installation and use are convenient, and the measurement is relatively accurate.
Steam Flow Measurement - Vortex Flowmeter:
The use of vortex flowmeters is actually mostly used for the measurement of steam flow in the market. It is cost-effective and can meet on-site measurement. The vortex flowmeter used to measure steam generally needs to have temperature and pressure compensation, because the temperature and pressure of the steam are changing at any time, and the density value of the steam can only be calculated by measuring the accurate temperature and pressure, so that The calculated mass flow is accurate. Temperature and pressure compensation is generally divided into integrated compensation and split compensation. The advantage of integrated compensation is that the installation is convenient and beautiful, but the accuracy is affected. Because the temperature and pressure of the integrated type are not in direct contact with the medium. However, this deviation is also related to the product design and quality of various manufacturers. For example, our company's temperature sensor is installed at the bottom of the probe, and there is almost no deviation in practice, and the pressure deviation is also very small. Of course, compared with the integrated type, the split-type vortex flowmeter is more accurate. It installs the temperature transmitter and the pressure transmitter separately on the pipeline for measurement, and the measurement result is closer to the real value.
Selection of flowmeter:
1. The flowmeter should be used within the technical parameters of the medium working pressure and temperature range. Do not deliberately choose instruments with high pressure level and ultra-high temperature, and choose instruments according to the actual working pressure and temperature, because the price of the latter is higher.
2. The selection of the flowmeter should not use the flow rate to work at the lower limit value as much as possible, so the diameter of the flowmeter should be as small as possible to obtain a larger flow rate and flow range.
3. The lower flow rate of the vortex flowmeter depends on the working density and kinematic viscosity of the medium, and its upper limit flow rate is generally not affected by the medium pressure and temperature. Therefore, to determine the flow range, it is only necessary to determine the actual available lower flow rate. After calculating the lower limit flow, check the flow range table to determine the corresponding diameter.